# Restaurant fire suppression system requirements and Class K extinguishers

> When a kitchen hood needs a fire suppression system, what it shuts off, where the pull station and Class K extinguisher go, and how often both are serviced.

Last updated: 2026-11-22

When a kitchen hood needs a fire suppression system, what it shuts off, where the pull station and Class K extinguisher go, and how often both are serviced.

By [Wobistro editorial team](https://wobistro.com/editorial-standards/) Published November 22, 2026 · 10 min read

## Short answer

A hood that serves grease-producing appliances, such as fryers, griddles and charbroilers, must be protected by an approved automatic fire-extinguishing system, usually a UL 300 wet-chemical system. When it fires it shuts off the fuel and power to the appliances under the hood. The manual pull station goes 10 to 20 feet from the hood by an exit, a Class K extinguisher goes within 30 feet of the cooking, and the system is serviced at least every 6 months.

[Exhaust hood sizes and options](https://wobistro.com/kitchen/equipment/exhaust-hood/)

*A griddle and fryer line under one hood, laid out in Wobistro. Open this venue in 3D*

## When a kitchen needs a suppression system

The 2025 California Fire Code, as summarised in a Newberry Springs Fire Department handout, requires a Type I hood over commercial cooking appliances that produce grease vapors, and says each hood and duct system that requires a Type I hood must be protected by an approved automatic fire-extinguishing system [[1]](https://wobistro.com/#source-nsfd). A City of Bellevue handout, written in 2011 for Washington, says a Type I hood goes at or above all commercial cooking appliances that produce grease-laden vapors, and lists deep fat fryers, griddles, broilers, hot-top ranges and charbroilers among them [[2]](https://wobistro.com/#source-bellevue). Our guide to [commercial kitchen hood requirements](https://wobistro.com/blog/commercial-kitchen-hood-requirements/) explains Type I and Type II hoods and how exhaust is sized.

The California handout lists a few narrow exceptions to the Type I hood itself: a hood listed to UL 710, a listed recirculating system, a listed integral downdraft, and certain electric appliances tested to emit very little grease [[1]](https://wobistro.com/#source-nsfd). These depend on the exact listing, so confirm them with the fire code official before you rely on one.

## What the system is and what it does

The system that the code recognises for commercial cooking is a pre-engineered wet-chemical system tested to UL 300; Washington’s adoption of IFC 904.13 says so directly: pre-engineered automatic dry- and wet-chemical extinguishing systems shall be tested in accordance with UL 300 [[3]](https://wobistro.com/#source-wac). The California handout adds that carbon dioxide systems and specially listed sprinkler systems are also recognised, and that new wet-chemical systems must follow NFPA 17A and the manufacturer’s listing [[1]](https://wobistro.com/#source-nsfd). An International Code Council training handout explains that NFPA 17A was developed to address UL 300 systems, and that the agent is a potassium carbonate solution mixed with water that cools the fire and interrupts the chemical chain reaction [[4]](https://wobistro.com/#source-icc).

Three parts matter for the layout:

- **Detection and nozzles.** Nozzles are aimed at specific appliances and at the hood plenum and duct. Thornton, Colorado, requires nozzles to be placed per the manufacturer’s listed manual and approved plans, with a means such as wheel stops or floor markings to keep each appliance under its nozzle [[5]](https://wobistro.com/#source-thornton).
- **Automatic and manual release.** Systems must actuate automatically and, with few exceptions, also have a manual pull station [[1]](https://wobistro.com/#source-nsfd).
- **Fuel and power shutoff.** On actuation, all sources of fuel and electric power that produce heat to every appliance protected by the system are shut down. Thornton adds that gas appliances not needing protection but under the same ventilation equipment must also be shut down, and that the shutoff devices require manual resetting before fuel or power returns [[5]](https://wobistro.com/#source-thornton). California words it the same way, with a manual reset after actuation [[1]](https://wobistro.com/#source-nsfd).

Where a building fire alarm system exists, the handouts say the extinguishing system is connected to it and monitored [[5]](https://wobistro.com/#source-thornton)[[1]](https://wobistro.com/#source-nsfd). Culver City’s plan notes add that the hood exhaust fan keeps running after activation unless a listed component or the system design requires it to stop [[6]](https://wobistro.com/#source-culver).

## The manual pull station

The pull station is the part of the system staff touch, so its position is a layout decision. The California handout and Thornton’s IFC 904.13.1 summary agree [[1]](https://wobistro.com/#source-nsfd)[[5]](https://wobistro.com/#source-thornton):

| Item | Requirement |
|---|---|
| Location | At or near a means of egress from the cooking area, readily accessible and unobstructed |
| Distance from the kitchen exhaust system | Not less than 10 ft (3 m) and not more than 20 ft (6 m) |
| Mounting height | Between 42 and 48 in (1.07 to 1.22 m) above the floor |
| Labelling | Clearly identifies the hazard protected |
| Operating effort | Up to 40 lb of force and 14 in of movement |

The 40-pound and 14-inch limits appear in both the California and the Bellevue handouts [[1]](https://wobistro.com/#source-nsfd)[[2]](https://wobistro.com/#source-bellevue). Culver City states the height as no higher than 4 feet above the finished floor, measured at the hood edge for the 10 to 20 foot distance, and requires a permanent sign when several pull stations serve several systems [[6]](https://wobistro.com/#source-culver). California also lets the fire code official approve another unobstructed location at or near the exit, in view from it, where the 10 to 20 foot spot is not practical [[1]](https://wobistro.com/#source-nsfd). Raise this early: the position of the line, the exit door and the hood decides whether a compliant pull station location exists.

## Class K extinguishers

Portable extinguishers are separate from the hood system. The fire code requires them within a 30-foot travel distance of commercial cooking equipment, and cooking that involves solid fuels or vegetable or animal oils and fats needs a Class K rated extinguisher [[2]](https://wobistro.com/#source-bellevue)[[5]](https://wobistro.com/#source-thornton). The California handout adds that the extinguisher must be compatible with the agent in the hood system and counts the 30 feet as travel distance, not straight-line distance [[1]](https://wobistro.com/#source-nsfd). Culver City says the inspector decides the placement, and requires a placard reading “Fire Protection System Shall Be Activated Prior To Using The Fire Extinguisher” [[6]](https://wobistro.com/#source-culver). Thornton requires the same instructions posted adjacent to each Class K extinguisher [[5]](https://wobistro.com/#source-thornton).

How many you need depends on the line. The 2025 California Fire Code handout lists these minimums [[1]](https://wobistro.com/#source-nsfd):

| Cooking hazard | Minimum Class K provision |
|---|---|
| Up to four deep-fat fryers, each holding up to 80 lb of cooking medium | One listed Class K extinguisher of at least 1.5 gal |
| Each additional group of up to four such fryers | One more listed Class K extinguisher of at least 1.5 gal |
| Solid-fuel appliance with a firebox of 5 cu ft or less | One 2.5 gal Class K wet-chemical extinguisher, or two 1.5 gal |
| A single fryer with more than 6 sq ft of surface | Installed per the extinguisher manufacturer’s recommendations |

Culver City’s notes also say more units may be required for solid-fuel equipment or multiple fryers of 6 sq ft or more [[6]](https://wobistro.com/#source-culver). OSHA’s portable extinguisher rule for workplaces does not mention Class K, but it does require extinguishers to be visually inspected monthly and to have an annual maintenance check, which applies to the Class K unit like any other [[7]](https://wobistro.com/#source-osha).

## Plans, permits and acceptance testing

Installing or changing the system is permitted work. The California handout says a construction permit is required to install or modify an automatic fire-extinguishing system other than a sprinkler system, that the fire code official may require construction documents, and that the system must pass an acceptance test before final approval [[1]](https://wobistro.com/#source-nsfd). Thornton asks the installer to keep the permit, approved shop drawings and manufacturer specifications on site, give four business days’ notice for the final test, and not start cooking until approval; the acceptance test covers the nozzles, automatic and manual activation with the shutdown of fuel and heat, ventilation start-up, an air test of the piping and fire alarm monitoring [[5]](https://wobistro.com/#source-thornton). Culver City requires a licensed contractor and asks for the manufacturer’s manual on site, with inspection rescheduled if it is missing [[6]](https://wobistro.com/#source-culver).

For the plan itself, Culver City’s notes list the code basis the plans must state (UL 300, NFPA 17A, NFPA 96 and the adopted fire and mechanical codes) and the plan notes for nozzles, pull stations, shutdown and extinguishers [[6]](https://wobistro.com/#source-culver). This is the fire department’s part of the review; the health department’s review is separate, and [health department plan review](https://wobistro.com/blog/health-department-plan-review/) describes it. Sequence both so the equipment schedule on each set of drawings matches.

## Inspection and service intervals

The California handout sets these intervals for the suppression system itself [[1]](https://wobistro.com/#source-nsfd):

- Wet-chemical systems are inspected and tested at six-month intervals and serviced at least every six months and after any activation.
- The six-month test covers the detection system, alarms, releasing devices and manual stations.
- Qualified individuals do the work and a certificate of inspection goes to the fire code official.

Culver City says the same: service at least every six months, or after activation, by a qualified or certified technician [[6]](https://wobistro.com/#source-culver), and Bellevue’s older handout says the same period applies to service or testing [[2]](https://wobistro.com/#source-bellevue). Hood and duct cleaning runs on a separate clock set by the type of cooking: every 3 months for high-volume operations such as 24-hour cooking, charbroiling or wok cooking; every month for solid-fuel appliances; every 6 months for most other kitchens; and every 12 months for low-volume operations [[1]](https://wobistro.com/#source-nsfd). Records stay on the premises, and California requires a conspicuous service tag with the provider’s details and the date [[1]](https://wobistro.com/#source-nsfd).

## Layout consequences

The suppression system is designed for the line as drawn, so the layout and the system change together. Fire departments say so plainly. The California handout says that when cooking equipment is repositioned the system must be evaluated and modified so the protected hazard still matches the listing, and that moving an appliance away from its listed nozzle coverage, changing the fryer size or swapping one appliance type for another can require a redesign [[1]](https://wobistro.com/#source-nsfd). Bellevue and Culver City say the same about changes to cooking media and equipment on an existing system [[2]](https://wobistro.com/#source-bellevue)[[6]](https://wobistro.com/#source-culver). In practice:

- **Draw the final appliance list before the system.** Each nozzle is aimed at an appliance of a given size and type.
- **Fix the position of anything on casters.** Thornton requires wheel stops or floor markings so a moved appliance returns under its nozzle [[5]](https://wobistro.com/#source-thornton). California also requires a listed connector and a restraining device on gas appliances on casters [[1]](https://wobistro.com/#source-nsfd).
- **Plan the exit route before the pull station.** A station 10 to 20 feet from the hood and at a way out of the cooking area has to be reachable without crossing the fire.
- **Keep the Class K extinguisher on the way out, not behind the line.** The 30-foot distance is travel distance, so walls and equipment count.
- **List every gas and electric appliance under the hood.** Equipment under the same hood is shut off together when the system fires [[5]](https://wobistro.com/#source-thornton).

## Worked example: a 60-seat fast-casual line

Wobistro’s simulator plans a fast-casual kitchen for 60 seats with a griddle, 2 fryers and one exhaust hood about 6.9 ft long, all under that hood. That is one hazard zone served by one system and one set of shutoffs. Under the California table above, 2 fryers that each hold up to 80 lb of oil need one Class K extinguisher of at least 1.5 gal, because they fall in the first group of four; a fifth fryer would add another. The simulator does not model oil capacity, so check the weight on the fryer you actually buy. See the [exhaust hood sizes and options](https://wobistro.com/kitchen/equipment/exhaust-hood/) and the [equipment catalogue](https://wobistro.com/kitchen/equipment/) for how Wobistro places hoods and the appliances beneath them, then test line positions in the [studio](https://wobistro.com/studio/?view=rooms) before you commit to a drawing. The pull station and extinguisher positions are marked on the drawings you submit to the fire department.

## Fire suppression checklist for the plan

- Ask the fire code official which edition of the fire code and NFPA 96 applies and what plans they want.
- Fix the appliance list and positions under each hood, including anything on casters.
- Choose a UL 300 wet-chemical system from a licensed fire protection contractor.
- Mark the pull station 10 to 20 ft from the hood, near an exit, 42 to 48 in above the floor.
- Place a Class K extinguisher within 30 ft of travel distance, with the activation placard beside it.
- List every gas and electric appliance to be shut down when the system discharges.
- Pull the permit, keep the approved drawings on site and schedule the acceptance test before opening.
- Book the six-month service and the hood cleaning schedule before you open.

## Work it out for your venue

- [Exhaust hood sizes and options](https://wobistro.com/kitchen/equipment/exhaust-hood/)Hood lengths, types and the appliances under them, as Wobistro places them in a kitchen plan.
- [Commercial kitchen equipment catalogue](https://wobistro.com/kitchen/equipment/)Sizes, utilities and simulator capacity for each equipment family Wobistro can place in a plan.
- [Open the Wobistro studio](https://wobistro.com/studio/?view=rooms)Start from photos, a floor plan or an example venue and edit it in 3D, with the simulator built in.

## Questions

### Does every restaurant need a fire suppression system?

A restaurant needs one over every hood that serves appliances producing grease-laden vapors, such as fryers, griddles, charbroilers, ranges and woks. A kitchen that only reheats or bakes may fall under different rules, so the fire code official decides for your appliances.

### What does a restaurant fire suppression system do when it goes off?

It discharges wet chemical onto the appliances and the hood, and it shuts off the fuel and electric power to the protected equipment. The shutoff must be reset by hand before gas or power is restored, so staff cannot restart the line by accident.

### Where must the Class K fire extinguisher be?

Within 30 feet of travel distance of the commercial cooking equipment, with a sign next to it telling staff to activate the hood system before using the extinguisher. The fire inspector can decide the exact spot, and fryers or solid-fuel appliances can require more than one.

### How often must a restaurant fire suppression system be inspected?

Wet-chemical systems are tested and serviced at least every 6 months and after any discharge, by a qualified person. Hood and duct cleaning follows a separate schedule that runs from monthly for solid fuel up to yearly for low-volume cooking.

### Do I need a permit to install or change a suppression system?

Usually yes. The California fire code handout calls for a construction permit to install or modify the system, and fire departments review plans before work starts. Call the fire code official before you move an appliance, because changes can require a redesigned piping layout.

### What happens if I move a fryer or change the oil under the hood?

Both can break the match between the appliance and the system’s listed nozzle coverage. Fire departments ask for the system to be evaluated and modified when equipment is repositioned or replaced, and some ask for plans to be submitted before the change.

## Limits of this guide

This guide explains the International Fire Code as adopted in the named examples (California 2025, Thornton, Colorado on the 2021 edition, and older Washington handouts) and what the cited fire departments publish. It does not reproduce NFPA 96 or NFPA 17A, which are not freely readable. The fire code official where you build decides which code edition applies, what plans to submit and where each device goes, and a licensed fire protection contractor designs and installs the system.

## Sources

1. Newberry Springs Fire Department (California), [Commercial Kitchen Systems: 2025 California Fire Code handout](https://newberryspringsfd.specialdistrict.org/files/ccc38234f/Commercial%2520Kitchen%2520Systems.pdf), Sections 1 to 12: Type I hood and suppression, actuation, shutoff, service, equipment changes, Class K. Accessed November 22, 2026.
2. City of Bellevue Fire Prevention Division (Washington), [Commercial Cooking, Public Information Handout F-51 (March 2011)](https://bellevuewa.gov/sites/default/files/media/pdf_document/F-51_CommercialCooking.pdf), Where required, extinguishing systems, portable extinguishers. Accessed November 22, 2026.
3. Washington State Legislature, [WAC 51-54A-0904: Fire code section 904 as adopted in Washington](https://lawfilesext.leg.wa.gov/Law/WAC/WAC%20%2051%20%20TITLE/WAC%20%2051%20-%2054A%20CHAPTER/WAC%20%2051%20-%2054A-0904.htm), Section 904.13, Commercial cooking systems. Accessed November 22, 2026.
4. International Code Council, [Type I Hoods and Commercial Cooking Operations (2019 Annual Conference educational handout)](https://www.iccsafe.org/wp-content/uploads/Type-I-Hoods-Commercial-Cooking-Operations.pdf), Slides on NFPA 17A, UL 300 and wet-chemical systems. Accessed November 22, 2026.
5. City of Thornton Fire Prevention Division (Colorado), [General Requirements for Commercial Cooking Fire Suppression Systems (TFD-FPD #034)](https://www.thorntonco.gov/sites/default/files/2024-06/TFD-FPD%23034%20Gen%20Req%20for%20Com%20Cooking%20Fire%20Supres%20Syst%20REVISED.pdf), Pages 1 and 2: IFC 904.13 manual actuation, nozzles, shutdown, acceptance test. Accessed November 22, 2026.
6. Culver City Fire Department (California), [Fire Extinguishing for Commercial Cooking: plan notes](https://www.culvercityfd.gov/Fire-Services/Community-Risk-Reduction/Plan-Notes/Fire-Extinguishing-for-Commercial-Cooking-Notes), Plan notes, pull stations, Class K, service, changes to existing systems. Accessed November 22, 2026.
7. U.S. Occupational Safety and Health Administration, [29 CFR 1910.157, Portable fire extinguishers](https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.157), 1910.157(e)(2) and (e)(3), inspection and maintenance. Accessed November 22, 2026.

Figures marked as Wobistro estimates come from the simulator defaults described in [our methodology](https://wobistro.com/methodology/). Found an error? [Tell us](https://wobistro.com/contact/) and we will correct it under our [editorial standards](https://wobistro.com/editorial-standards/).

## Related guides

More on commercial kitchen design

- [Commercial kitchen hood requirements: Type I, Type II and airflow](https://wobistro.com/blog/commercial-kitchen-hood-requirements/)When a restaurant needs a Type I or Type II hood, how far it must overhang, clearances, and how exhaust airflow is set, with a worked sizing example.Commercial kitchen designNovember 22, 20267 min read
- [Commercial kitchen layout: how to choose one for your menu](https://wobistro.com/blog/commercial-kitchen-layout/)The five common commercial kitchen layouts, how food should move from receiving to the pass, and how to choose a layout from your menu, volume and space.Commercial kitchen designNovember 22, 20268 min read
- [Health department plan review for restaurants: what to submit](https://wobistro.com/blog/health-department-plan-review/)What health departments ask for before you build or remodel a restaurant: plans, menu, equipment and finish schedules, review times and inspections.Opening a restaurantNovember 22, 20267 min read
- [Make-up air requirements for restaurants and commercial kitchens](https://wobistro.com/blog/make-up-air-requirements/)Why a kitchen hood needs make-up air, how much, tempered or not, interlocks, transfer air, energy code limits and where the unit goes, with an 80-seat example.Commercial kitchen designNovember 22, 202610 min read

---
Source: https://wobistro.com/blog/restaurant-fire-suppression-system/