Commercial kitchen hood requirements: Type I, Type II and airflow
When a restaurant needs a Type I or Type II hood, how far it must overhang, clearances, and how exhaust airflow is set, with a worked sizing example.
Short answer
Appliances that produce grease or smoke, such as fryers, griddles, ranges and broilers, go under a Type I hood with grease filters and a fire suppression system. Appliances that give off only heat or steam, such as steamers, kettles and dish machines, need a Type II hood where the code calls for one. A canopy hood overhangs the appliances by at least 6 inches, and its exhaust is set in cubic feet per minute per foot of hood, by hood style and appliance duty or by the hood’s listing.

Type I or Type II: what goes under which hood
The International Mechanical Code, a model code that states and cities adopt with their own amendments, divides commercial kitchen hoods into two kinds. An International Code Council training handout covering the 2012 to 2018 editions summarises them: Type I hoods go where cooking appliances produce grease or smoke, and Type II hoods are installed above appliances that produce no grease or smoke, such as steam or moisture producers [1]. A Georgia Department of Public Health design manual, which quotes the 2006 edition as adopted in Georgia, gives typical examples: Type I over griddles, fryers, broilers, ovens, ranges and woks; Type II over steamers, kettles, pasta cookers and dishwashing machines [2].
The code also classes appliances by duty, which decides how much air the hood must move. In the ICC handout [1]:
| Duty | Examples |
|---|---|
| Extra-heavy | Appliances using solid fuel (wood, charcoal, briquettes, mesquite) as the primary heat |
| Heavy | Gas and electric underfired broilers, chain (conveyor) broilers, gas open-burner ranges, wok ranges, upright broilers and salamanders |
| Medium | Electric discrete-element and hot-top ranges, griddles, fryers, pasta cookers, conveyor pizza ovens, tilting skillets |
| Light | Ovens, steamers and small kettles (the Georgia manual’s light-duty examples) |
The hood is sized for the heaviest appliance under it. One charbroiler on a line of fryers makes the whole hood heavy duty, which is a good reason to group appliances of similar duty, or to give a wood-fired oven its own hood.
Size and position
In the same ICC summary, a canopy hood extends at least 6 inches beyond the edge of all the appliances under it and its lower edge sits no more than 4 feet above the cooking surface; a non-canopy hood sits no more than 3 feet above it. A Type I hood keeps 18 inches of clearance from combustible materials, or none from wallboard on a noncombustible support [1]. The Georgia manual repeats the 6-inch overhang and the 18-inch clearance [2].
In practice the hood length is the length of the hooded line plus the overhang at each open end. Wobistro’s simulator sizes the hood as the hooded line plus 0.3 m (about a foot), rounded up to the next 0.3 m, and the studio flags any appliance that sticks out past a hood’s 6-inch overhang when you place it.
How much air: code minimums and California’s maximums
Exhaust is set in cubic feet per minute per linear foot of hood. The code table summarised by the ICC gives minimum rates by hood style and duty [1]:
| Hood style | Extra-heavy | Heavy | Medium | Light |
|---|---|---|---|---|
| Wall-mounted canopy | 550 | 400 | 300 | 200 |
| Single island canopy | 700 | 600 | 500 | 400 |
| Double island canopy | 550 | 400 | 300 | 250 |
| Eyebrow | not allowed | not allowed | 250 | 250 |
| Backshelf or pass-over | not allowed | 400 | 300 | 250 |
These minimums apply to hoods that are not listed. The same handout lists UL 710 listed factory-built commercial exhaust hoods as an exception [1]: a listed hood has been tested and runs at the airflow on its listing, which can be lower than the table. Ask each supplier for the listed airflow of the hood you are considering.
California goes further for larger kitchens. Its energy code sets maximum exhaust rates for Type I hoods in Table 140.9-A, but only when the total Type I and Type II hood exhaust is greater than 5,000 cfm; the threshold was chosen to exempt small restaurants [3]. The California values are based on research with UL-listed hoods and are typically lower than the minimums for unlisted hoods, so a kitchen above the threshold will in practice need listed hoods. The limit does not apply where at least 75 percent of the hood makeup air is transfer air that would otherwise be exhausted, or to existing hoods that are not being replaced [3].
| Hood style | Light | Medium | Heavy | Extra-heavy |
|---|---|---|---|---|
| Wall-mounted canopy | 140 | 210 | 280 | 385 |
| Single island | 280 | 350 | 420 | 490 |
| Double island | 175 | 210 | 280 | 385 |
| Eyebrow | 175 | 175 | not allowed | not allowed |
| Back shelf or pass-over | 210 | 210 | 280 | not allowed |
Two more points from the California guidance apply anywhere: short-circuit hoods that supply more than 10 percent of the hood exhaust directly at the hood significantly reduce capture and containment, and excessive exhaust costs energy twice, once to exhaust the air and again to heat or cool the makeup air that replaces it [3].
Worked example: sizing the hood
The kitchen capacity calculator sizes the hood from the line it sizes. It plans with 250 cfm per foot for medium duty, × 0.7 for light duty and × 1.4 for heavy duty: a planning figure for a listed hood, between the unlisted minimum and the California maximum. Here it is for a burger-and-fries kitchen at two volumes, next to what the two tables would give for a wall-mounted canopy of the same length:
| Covers a day | Hood | Duty | Wobistro plan | Unlisted minimum | California maximum* |
|---|---|---|---|---|---|
| 300 | 5.9 ft | medium | 1,500 cfm | 1,750 cfm | 1,250 cfm |
| 600 | 6.9 ft | medium | 1,700 cfm | 2,050 cfm | 1,450 cfm |
* California’s maximum applies only above 5,000 cfm of total hood exhaust, so it would not apply to kitchens this size; it is shown for scale.
Add a charbroiler and the picture changes. The 80-seat casual restaurant in our equipment list guide, with a charbroiler, a range, a combi oven and a fryer, gets a 10.8 ft heavy-duty hood planned at about 3,800 cfm; an unlisted wall canopy would need at least 4,350 cfm. Every cubic foot of exhaust must be replaced by makeup air, heated in winter and cooled in summer, so the duty of the line is an operating cost, not just a construction one.
Fire suppression and NFPA 96
The ICC summary notes that a Type I hood and duct system must be protected by a fire suppression system [1]. The standard that tests these systems is ANSI/CAN/UL/ULC 300, Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment [4], which is why suppliers describe systems as “UL 300”. The installation, ductwork, clearances and cleaning of the whole system follow NFPA 96, the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations; the Georgia manual, for example, references its 2004 edition [2]. Fire marshals enforce the edition their jurisdiction has adopted, so ask before your mechanical design starts.
What plan reviewers want to see
The health department’s plan review asks for ventilation on the drawings alongside the equipment schedule [5]; the building or mechanical permit asks for the engineered design. Expect to show the hood type and listing, its length and overhang, the appliances under it with their duty, exhaust and makeup air quantities, the duct route to the roof and the suppression system. See health department plan review for the full submission.
Hood planning checklist
- List every appliance with its fuel and duty; mark which produce grease or smoke.
- Group appliances by duty so one heavy appliance does not make a whole long hood heavy.
- Keep all grease-producing appliances under the hood with 6 inches of overhang at each open end.
- Choose a listed hood and use its listed airflow; budget makeup air for the same quantity.
- Plan the duct route to the roof and the 18-inch clearance to combustibles before fixing the layout.
- Specify a fire suppression system tested to UL 300 and ask the fire marshal which NFPA 96 edition applies.
- In California, add up total hood exhaust: above 5,000 cfm, Table 140.9-A limits apply.
Try it on your own line: place equipment in the studio and the hood checks run as you go, or look up any appliance’s hood type, utilities and size in the equipment catalogue.
Work it out for your venue
- Kitchen capacity calculator
Fryers, griddle width and hood size from covers per day and your menu mix.
- Commercial kitchen equipment catalogue
Sizes, utilities and simulator capacity for each equipment family Wobistro can place in a plan.
- Open the Wobistro studio
Start from photos, a floor plan or an example venue and edit it in 3D, with the simulator built in.
Questions
What is the difference between a Type I and a Type II hood?
A Type I hood serves appliances that produce grease or smoke, such as fryers, griddles, ranges, broilers and woks, and has grease filters, a grease duct and fire suppression. A Type II hood serves appliances that give off heat, steam or moisture without grease, such as steamers, kettles, pasta cookers and dish machines.
How far does a kitchen hood need to overhang the cooking equipment?
In the International Mechanical Code rules summarised by the International Code Council, a canopy hood extends at least 6 inches beyond the edge of every appliance under it, with its lower edge no more than 4 feet above the cooking surface. Check the edition your jurisdiction adopted.
How many cfm per foot does a restaurant hood need?
It depends on the hood style, the hottest appliance under it and whether the hood is listed. The prescriptive minimums in the code table summarised by the ICC run from 200 to 550 cfm per foot for wall-mounted canopies; listed hoods run at the rate on their listing. Wobistro plans with 250 cfm per foot for medium duty.
What size hood does a burger and fries kitchen need?
For 300 covers a day with a burger-and-fries menu, Wobistro’s kitchen capacity calculator proposes a 5.9 ft medium-duty hood at about 1,500 cfm. Your mechanical engineer sizes the real hood from the appliances you buy and the hood’s listing.
Sources
- International Code Council, ICC Commercial Cooking Systems, 2012–2018 Overview (2019 Annual Conference educational handout), IMC §507 slides: definitions, hood details, ventilation rates. Accessed November 22, 2026.
- Georgia Department of Public Health, Food Service Establishment Manual for Design, Installation and Construction, Section Q: Ventilation, citing the 2006 International Mechanical Code as adopted in Georgia. Accessed November 22, 2026.
- Energy Code Ace (California Energy Commission program), Commercial Kitchens: Nonresidential Compliance Manual chapter, §140.9(b), Table 140.9-A. Accessed November 22, 2026.
- UL Solutions, Fire extinguishing system unit testing, Safety and performance standards. Accessed November 22, 2026.
- Conference for Food Protection (copy hosted by Montana DPHHS), Plan Review for Food Establishments, 2016, Contents and format of plans and specifications. Accessed November 22, 2026.
Figures marked as Wobistro estimates come from the simulator defaults described in our methodology. Found an error? Tell us and we will correct it under our editorial standards.