Make-up air requirements for restaurants and commercial kitchens

Why a kitchen hood needs make-up air, how much, tempered or not, interlocks, transfer air, energy code limits and where the unit goes, with an 80-seat example.

Short answer

Every cubic foot of air a kitchen hood exhausts has to come back into the building. The International Mechanical Code says make-up air from all sources must be approximately equal to the exhaust, supplied mechanically and interlocked so it runs whenever the exhaust runs. Make-up air can be transfer air from the dining room or outdoor air from a dedicated unit, and some codes require it to be tempered. Energy codes such as California’s limit how much conditioned make-up air a kitchen may use.

Kitchen capacity calculator

Aerial 3D view of a fast-casual burger restaurant with a service counter, a fryer and griddle line and a dining room
A burger kitchen next to its dining room in Wobistro: the room that gives transfer air to the hood. Open this venue in 3D

Why a hood needs make-up air

A hood is a fan that throws conditioned room air out of the roof. The air has to come from somewhere. The International Mechanical Code (IMC), section 508.1 in the 2024 edition, requires that the amount of make-up air supplied to the building from all sources be approximately equal to the exhaust air removed by all exhaust systems in the building, and that the make-up air system must not reduce the effectiveness of the exhaust system [1]. Georgia’s design manual quotes the same rule from the 2006 edition and adds that the air may be provided by gravity or mechanical means or both [2].

The same manual explains what goes wrong without it. The building would be under negative pressure, which could mean that [2]:

  • the exhaust fan cannot exhaust the design volume of air because the air is not available;
  • water heaters, space heaters and other individually vented gas appliances vent improperly;
  • a surge of unconditioned outside air enters whenever a door is opened, which may also let flies in.

A ventilation manufacturer’s article, which we cite as a vendor view and not as code, adds that a hood without make-up air can lose up to 30 percent of its exhaust volume, letting grease and smoke drift into the seating area [3]. The hood guide covers how much exhaust a hood needs; see commercial kitchen hood requirements. This guide starts where the exhaust figure ends.

Where the air can come from

The code says “all sources”, so make-up air can be assembled from several:

  • Transfer air from the dining room or other spaces, air that was already brought in for ventilation and would otherwise be exhausted. Energy Code Ace’s California worked examples subtract the toilet exhaust from the dining room’s outdoor air to find what is available to transfer [4].
  • A dedicated make-up air unit, a fan with a filter and, usually, a heating or cooling coil, supplying outdoor air to the kitchen.
  • The building’s HVAC. Georgia’s manual says air conditioning systems may also serve as a source of make-up air [2].
  • Doors, windows and louvers. Georgia says outside windows and doors shall not be used to provide make-up air [2], and the vendor article calls louver or door supply untempered and generally unfiltered [3].

The vendor article also cites IMC section 505 as requiring make-up air for hoods exhausting more than 400 cfm, and says rooftop-unit-only supply is common below 800 cfm of exhaust [3]. We could not open the IMC text for that threshold, so treat both numbers as the vendor’s reading and ask your plan reviewer what your edition says.

Tempered or untempered

Tempering means heating or cooling the make-up air. Codes treat it three ways:

Three treatments of tempering
RuleWhat it saysWhere
Capacity or 10°F ruleHVAC serving the kitchen must have capacity to offset the sensible and latent load of the make-up air, or a dedicated system must keep the supply within 10°F (6°C) of the kitchen design setpoint. Make-up air through compensating hoods is excepted.IMC §508.1.1, 2024 edition
Minimum temperatureMake-up air must be at least 50°F (10°C), measured where it leaves the supply diffuser. Compensating hoods must comply with NFPA 96 and ASHRAE 154.Minnesota amendment, 2020
Filtered, may be temperedReplacement air shall be filtered and may also be tempered by a separate control; velocity should be low enough to avoid drafts.Georgia manual, 2006 IMC

Sources: [1] [5] [2]. The Minnesota text shows a state raising or replacing the model rule, so the rule that applies is the one in your adopted code. Tempering is an operating cost as much as a first cost: the vendor article notes that heating and cooling more air than needed adds energy use, and that a make-up air unit that conditions only the air a kitchen needs saves energy [3].

Interlocks: the two fans start together

The 2024 IMC requires mechanical make-up air systems to start and operate simultaneously with the exhaust system [1]. Minnesota’s amendment says the two must be electrically interlocked, so that make-up air is provided whenever the exhaust system is in operation [5]. Georgia’s manual says the controls should be interlocked to ensure the units operate simultaneously [2].

In the vendor’s comparison, a make-up air unit interlocked with the exhaust fan supplies air only while the fan runs and gives the most control over building pressure, whereas a rooftop unit generally runs independently of the exhaust fan [3].

Building pressure

The goal is not zero pressure in the kitchen. Georgia’s manual says it is desirable to have the kitchen under a very slight negative pressure to prevent cooking odors from filtering into the dining room [2]. The vendor article describes a make-up air unit plus a rooftop unit bringing space pressure back to neutral or slightly negative [3]. That is why make-up air is “approximately” equal and not exactly equal: a balance, set during commissioning, where the kitchen pulls a little air from the dining room and the dining room pulls a little from outside.

The pressure also depends on every other exhaust fan in the building, which is why the IMC counts all exhaust systems, not just the hood [1]. Toilet exhaust counts too: the California examples subtract it from the dining room’s outdoor air [4].

Energy codes: limits on conditioned make-up air

Heating and cooling make-up air for a hood is one of a restaurant’s largest loads, and energy codes now limit it. California’s Title 24, as explained by Energy Code Ace, applies its kitchen exhaust requirements only when total Type I and Type II hood exhaust is greater than 5,000 cfm, a threshold chosen to exempt small restaurants [4]. Above it:

  • Mechanically cooled or heated make-up air delivered to a space with a kitchen hood may not exceed the greater of the supply flow required to meet the space heating or cooling load, or the hood exhaust minus the available transfer air from adjacent spaces [4].
  • The kitchen must meet one of several efficiency options, including at least 50 percent of replacement air as transfer air, or demand ventilation control on at least 75 percent of the exhaust air [4].
  • Demand ventilation controls must modulate airflow, fail to full flow on sensor failure, include an adjustable timed override, and reduce airflow to the larger of 50 percent of total design exhaust and replacement airflow or the general ventilation rate [4].
  • Short-circuit hoods, which blow make-up air straight into the hood, are limited to 10 percent of the hood exhaust rate [4].

The guidance includes a worked example: a 5,000 cfm hood where the kitchen needs 2,000 cfm of supply for its load, so the make-up air unit supplies 2,000 cfm and 3,000 cfm is transferred from the dining room [4]. Other states adopt the model energy codes with their own amendments, and we have not opened those texts here. If you build outside California, ask which energy code edition applies and whether it limits conditioned make-up air for kitchens.

Worked example: an 80-seat kitchen

Wobistro’s simulator plans a hood for each concept from its cooking line. For 80-seat venues with default menus it plans:

Hood exhaust planned for 80-seat venues, and what the California rules would mean
ConceptPlanned hood exhaust10% short-circuit limitCalifornia 5,000 cfm threshold
Fast casual1,950 cfm200 cfmbelow
Casual dining3,800 cfm400 cfmbelow
Café2,450 cfm250 cfmbelow
Bar750 cfm50 cfmbelow

The exhaust figure is the planning quantity the make-up air system has to match; the hood guide shows how it is derived. The short-circuit column is 10 percent of it, the most a California-style short-circuit hood could supply directly [4]. All four are below 5,000 cfm, so California’s kitchen exhaust limits would not apply to kitchens this size, but the IMC balance rule still does.

Take the casual restaurant, with its charbroiler, range, combi oven and fryer under one hood at about 3,800 cfm. The code asks for about 3,800 cfm of make-up air from all sources. The split depends on the building, so here are two illustrative cases, using the subtraction in the California rule [4]:

Make-up air unit load for a hood at about 3,800 cfm
Transfer air from the dining room (assumed)Left for the make-up air unit
1,000 cfm2,800 cfm
2,000 cfm1,800 cfm

The transfer figures are assumptions, not Wobistro outputs; the real value is the dining room’s outdoor air less its own exhaust, which the engineer calculates. The point is the sensitivity: more transfer air shrinks the make-up air unit and the conditioning load, which is why a kitchen next to a large dining room has an advantage over a ghost kitchen with no neighbour. Wobistro does not size make-up air units, tempering coils or controls; it gives the hood quantity to start from.

Where the make-up air goes in the plan

  • Near the hood, but not into it. Georgia’s manual says make-up air is frequently introduced at some point in close proximity to the hood to avoid removing conditioned air that has been heated or cooled [2]. California limits how much may be supplied directly at the hood [4], because the hood must still capture.
  • Low velocity. Georgia says velocity through the system should be low enough to avoid drafts [2]; keep diffusers away from the cook line and the hand sink.
  • A unit and a duct route. The make-up air unit, the exhaust fan and the rooftop equipment need roof space and structural support, and the supply duct has to reach the kitchen ceiling. Settle the route with the engineer before the ceiling height is fixed.
  • The intake. Keep it clear of the hood’s exhaust discharge; your mechanical code sets the separation distance, and we did not open that table.

The exhaust hood page shows the hood lengths and the appliances under them, the kitchen capacity calculator sizes the hood from covers per day, and the kitchen plans by concept show the ventilation zone in each layout. For the fire side of the same hood, see restaurant fire suppression systems.

Make-up air checklist

  • Take the hood exhaust from the hood schedule and add every other exhaust fan in the building.
  • Ask the building official which mechanical and energy code editions, and which amendments, apply.
  • Decide how much comes as transfer air from the dining room and how much from a dedicated unit.
  • Specify filtration, and tempering as your code requires: a capacity or 10°F rule, or a minimum supply temperature.
  • Interlock the make-up air fan with the exhaust fan so the two start and stop together.
  • Supply near the hood at low velocity, with no more than your code allows directly at the hood.
  • Plan the roof space, duct route and intake location before fixing ceiling heights.
  • Have the engineer balance the system so the kitchen sits slightly negative to the dining room.

Work it out for your venue

Questions

How much make-up air does a commercial kitchen need?

Approximately as much as is exhausted. The International Mechanical Code, as summarised by the ICC, requires make-up air from all sources to be approximately equal to the exhaust removed by all exhaust systems in the building. For an 80-seat casual restaurant, Wobistro’s simulator plans a hood at about 3,800 cfm.

Does a restaurant need a make-up air unit?

Not always as a separate unit. The code asks for make-up air that equals the exhaust, and it may come from transfer air out of the dining room or from outdoor air supplied by an HVAC system. A vendor article says that above a certain exhaust volume louvers or doors give poor control, so a dedicated unit is common.

Does make-up air have to be heated?

Not under the base model code, which sets a limit instead. The 2024 International Mechanical Code requires either enough HVAC capacity to offset the load of the make-up air or conditioning that keeps it within 10°F of the kitchen setpoint, with an exception for compensating hoods. Minnesota’s amendment sets a minimum supply temperature, so local rules vary.

What happens if a kitchen has no make-up air?

The building goes under negative pressure. Georgia’s design manual lists the results: the exhaust fan cannot move its design volume, gas appliances may vent badly, and outside air surges in when doors open. A vendor article adds that the exhaust drops and hood capture suffers.

What is transfer air?

Air that moves from an adjacent space, such as the dining room, into the kitchen, where it replaces what the hood exhausts. California’s energy code guidance counts it as make-up air that would otherwise have been exhausted, and it limits mechanically conditioned make-up air when transfer air is available.

Sources

  1. International Code Council, Exhaust systems and makeup air: achieving balance under the 2024 International Mechanical Code (Building Safety Journal), IMC §508.1 and §508.1.1. Accessed November 22, 2026.
  2. Georgia Department of Public Health, Food Service Establishment Manual for Design, Installation and Construction, Section Q: Ventilation, VIII. Make-Up Air (quoting the 2006 IMC as adopted in Georgia). Accessed November 22, 2026.
  3. Greenheck (a ventilation equipment manufacturer), When is make-up air required for kitchens?, Vendor article on louver, rooftop and make-up air unit supply. Accessed November 22, 2026.
  4. Energy Code Ace (California Energy Commission program), Commercial Kitchens: Nonresidential Compliance Manual chapter 10.3, §140.9(b) replacement air, transfer air and demand ventilation; examples 10-1 to 10-4. Accessed November 22, 2026.
  5. Minnesota Office of the Revisor of Statutes, Minnesota Rules 1346.0508, Section 508 Commercial Kitchen Makeup Air (2020 version), State amendments to IMC §508.1, §508.1.1 and §508.2. Accessed November 22, 2026.

Figures marked as Wobistro estimates come from the simulator defaults described in our methodology. Found an error? Tell us and we will correct it under our editorial standards.